The objective of this assignment is to investigate some aspects ofpower system frequency con- trol using simplified models. The investigation is intended to provide conceptual insights only. The models are not necessarily optimized to yield the best frequency control performance. The Mathworks Simulink program, which is a companion of Matlab, will be employed to build and simulate dynamic models of the systems. Thus, the assignment will also provide an opportunity for you to become familiar with a very widely used tool for simulating dynamic systems.
The deliverable outcome is to be an engineering report that clearly and concisely details the con- duct and findings of your investigation and clear and pointed discussion of the technical and en- gineering significance of your findings. The report should address each of the matters and questions listed in the scope of work in Section 3. Credit will be given for innovative studies and analysis that either reveal other aspects of system performance or which improve the per- formance of the system.
It is recommended that you follow the guidelines for writing technical engineering reports pro- duced by Monash University and which are available at the following web-site:
https://www.monash.edu/rlo/assignment-samples/engineering/eng-writing-technical-reports
With reference to the above guidelines your report is expected to convey information to other engineers about key aspects of the performance of the system and it is intended for selective reading. The latter point means that you should organize your report into numbered sections with informative headings.
It is strongly recommend that you approach this assignment in the same way as you would as a professional engineer conducting the project for an employer or client.
Introductory analysis is presented in Section 1 to assist in the systematic formulation of the fre- quency control model.
The objective is to explore the performance of the system frequency control system as the mix of generation sources is varied. We are interested in assessing performance for different propor- tions of synchronous and asynchronous generation and how the performance of the frequency control system performs as different proportions of generation capacity are equipped with pri- mary frequency control. The overall structure of the system model is shown in Figure 1. In this model the equivalent generator model represents the effective inertial response of the system taking into consideration that a proportion of the generation is asynchronous. A proportion of both the synchronous and asynchronous generation sources are not equipped with frequency controls and therefore do not contribute to the control of system frequency. A proportion of syn- chronous sources are equipped with governors which control the speed of their generators and a proportion of asynchronous sources are also equipped with frequency controllers that are used to regulate their power output so as to control system frequency.
|
|
P msp |
|
P m |
|
|
|
Turbine Governor
Synchronous Ungoverned Generation Asynchronous
|
x |
|
Equivalent Generator |
||||
|
PL0
|
||||||
|
|||||||
f |
|||||||
|
|||||||
P map |
|||||||
|
Figure 1: Simplified model of system frequency control containing synchronous and
asynchronous sources. (Note that blocks with no input signal represent a fixed or constant
input to the model with the value shown in the block.)
1.1 Per-unit scaling and specification of generation capacities
We will use the total online generation capacity (Sb in MW) as the base value of power. Thus, a power system load, Pl , of 0.8 per-unit means that the system is consuming 80% of the rated on-line generation capacity. (Note: We will see below that it is not necessary to specify the ac- tual value of Sb).
To facilitate this exploration the total online generation capacity is divided into a number of components.
Sb = Ssb + Sab (1)
where Ssb and Sab are respectively the online synchronous and online non-synchronous (or asynchronous) generation capacity.
Ssb = asbSb and Sab = ( 1 – asb)Sb (2)
where asb is the specified proportion of the total online generation capacity which is synchro-
nous.
The online synchronous generation capacity is then partitioned into the following components: Ssb = Sspb + Ssub where (3)
Sspb = aspbSsb = aspb asbSb and Ssub = ( 1 – aspb)Ssb = ( 1 – aspb)asbSb (4)
are respectively the proportion of online synchronous generation capacity with primary govern- ing control and the balance of online synchronous generation capacity is ungoverned.
The online asynchronous generation capacity is similarly partitioned into a fraction with prima- ry governing control, Sapb , and the balance of asynchronous generation which is ungoverned, Saub , where:
Sab = Sapb + Saub and (5)
Sapb = apb Sab = apb( 1 – sb)Sb (6)
Saub = ( 1 – apb)Sab = ( 1 – apb)( 1 – sb)Sb
Thus, to define the online capacities of the different types of generation represented in our mod- el the parameters sb , spb and apb must be specified.
For example, if sb = 0.8 then 80% of all online generation capacity is synchronous and the balance 1 – sb = 0.2 (i.e. 20%) is asynchronous. If spb = 0.4 then 40% of the online syn- chronous generation capacity is under primary frequency control and the balance of such gen- eration (i.e. 60%) is not under frequency control. In this example it means that sb spb = 0.8 0.4 = 0.32 or just 32% of all online capacity is under primary frequency control.
1.2 Specification of the initial generation output
In this model we specify the initial power output from each of the generation sources. On the basis of this specification the initial system load is determined, on the assumption that the sys- tem is lossless.
The initial power output from the online synchronous generation with primary speed control is specified as a fraction sp of the specified online capacity Sspb of this type of generation. The initial power output is expressed in per-unit of Sb .
Pmsp0 = sp SspbSb = sp spbSsbSb = sp ( spb sb) in pu of Sb
(7)
The initial power output from the synchronous generation sources is:
P = P + P
and the initial power output from the asynchronous generation sources is:
P = P + P
(9)
(10)
and finally, the initial output from all generation sources is,
P = P + P . (11)
Thus, to define the initial steady-state operating point of the system it is necessary to specify bsp, bsu, bap and bau .
It is important to distinguish between online capacity of the various generation categories and the actual (initial) power output from each of these generation categories. Thus, if, for example, bsp = 0.5 then it means that initially the power output of the online synchronous generation capacity that is under primary frequency control is 50%. If, furthermore, ab = 0.8 and aspb = 0.4 it follows that the initial power output from all online synchronous generation ca- pacity that is under primary frequency control is:
Pmsp0 = bsp (aspb ab) = 0.5 根 (0.8 根 0.4) = 0.16 pu of Sb .
1.3 Equivalent generator rotor dynamics
The transfer-function block diagram of the equivalent generator of the system is shown in Fig- ure 2.
m +
-
Pl
D L |
编Pl0
+
Pl0 |
Figure 2: Equivalent generator rotor dynamics for system
load / frequency analysis.
1.3.1 Specification of the inertia constant
The inertia constant of online synchronous generation limits the rate of change of frequency. In the model we specify the inertia constant, Hs, in per-unit of the on-line synchronous generation capacity. Typically, Hs = 3.5 pu on Ssb .
H = Hs SsbSb)) = asbHs ( 12)
1.3.2 Frequency dependent load
The system load is linearly dependent on the system-frequency perturbation as follows
Pl (f) = (Pl0 + Pl0 )( 1 + D f) (13)
where f = ( 1 + f) pu is the system frequency in per-unit of the system nominal synchronous frequency, f0 = 50 Hz, f is the per-unit perturbation of the system frequency and Pl0 is the initial steady-state value of the load. Note that under initial steady-state conditions the system is operating at synchronous frequency, i.e. f0 = 0 pu. Pl0 is the initial steady-state load on the system assuming that the system is initially operating at 50 Hz; and Pl0 is the applied change in system load at the nominal system frequency of 50 Hz
1.3.3 Composite rotor equation of motion for the analysis of system-frequency controls The acceleration equation of the system is, as detailed in the lectures,
2Hdfdt = Pm – Pl in pu of Sb (14)
where Pm and Pl are respectively the generation and load, f is the per-unit system-frequency perturbation and H is as defined in (12). The block diagram of this equation, including the fre- quency dependence of the load, is shown in Figure 2.
1.4 Synchronous generator turbine-governor model
The block diagram of the synchronous generator turbine governor system employed in the as- signment is shown in Figure 3. This block diagram shows the conversion from per-unit quanti- ties on the system MVA base, Sb , at the input and output from the model to per-unit quantities on the turbine rated capacity, Sspb , within the turbine-governor model. The block diagrams of the governor and turbine models are shown respectively in Figures 4 and 5. The turbine model is representative of a steam turbine which is presently the most commonly deployed turbine in
Australia.
f
1 R – Droop – pu on Sspb
pu on Sb pu on Sspb pu on Sspb pu on Sb
Figure 3: Synchronous generator turbine-governor model including base conversions at the
turbine / governor model interfaces. (Note: Pref = Pmsp0 is the turbine load reference and is
represented as an external input. In Simulink such an external input can be represented as a
constant block).
1
LR
g +
-----
T
g
LL
0
Figure 4: Governor model (i.e. the block GOV in Figure 3).
HP |
LP |
一
HP flow
F |
FHP, FIP, FLP
turbine power
fractions.
Figure 5: Turbine model (i.e. the block TURB in Figure 3).