ELEC4310 Power Systems Analysis Semester One Examinations, 2022
Hello, dear friend, you can consult us at any time if you have any questions, add WeChat: daixieit
Semester One Examinations, 2022
ELEC4310 Power Systems Analysis
Question 1.
15 Marks
A three phase transmission line is 480-km long and serves a load of 400 MVA, with 0.8 lagging power factor at 345 kV. The ABCD constants of the line are:-
A=D= 0.8180三1.3o
B= 172.2三84.2o Ω
C= 0.001933三90.4o S
(a) Determine the sending-end line to neutral voltage, the sending-end current,
and the percentage voltage drop at full load. (4 Marks)
(b) Determine the receiving-end line to neutral voltage at no load, the sending-
end current at no load and the voltage regulation. (6 Marks)
(c) A series capacitor bank having a reactance of 146.6 Ω is to be installed at the mid-point of the 480 km line above. The ABCD constants for each of 240km
portion of lines are:-
A=D= 0.9534三0.3o
B= 90.33三84.1o Ω
C= 0.001014三90.1o S
Determine the equivalent ABCD constants for the cascaded combination of the line-capacitor-line using the formula given below, where (A1 B1 C1 D1 ) is in
cascade with (A2 B2 C2 D2) (5 Marks)
A= A1A2+ B1C2 ; B=A1B2+B1 D2 C= A2C1+C2 D1 D=B2C1+D1 D2
Question 2.
15 Marks
Figure 1 shows the one-line diagram of a simple three-bus power system with generators at buses 1 and 3. The magnitude of voltage at bus 1 is adjusted to 1.05 pu. Voltage magnitude at bus 3 is fixed at 1.04 pu with a real power generation of 200 MW . A load consisting of 400 MW and 250 Mvar is taken from bus 2. Line impedances are marked in per unit on a 100 MVA base and the line charging susceptance’s are neglected.
Figure 1
(a) Determine the bus admittance matrix-Y of the system shown in Figure 1.
Determine the Bus susceptance matrices B’ and B’’ for this power
system. (4 Marks)
.
(b) Determine the Values of V2三62 and 三63 using Decouple Load flow
algorithm after the first iteration. (5 Marks)
Where the elements of the Jacobian matrix with the initial estimate are given below.
54.28 −33.28 24.86
−27. 14 16.64 49.72
(c) Determine the Values of V2三62 and 三63 using Fast Decouple load flow algorithm after the first iteration. (4 Marks)
(d) Calculate P1 and Q1 , with the bus voltage solutions obtained from (b). (2 Marks)
Question 3.
15 Marks
A single line diagram of a power system is shown in Figure 2, where positive, negative and zero sequence reactances are given. Where positive sequence impedances are not given, they can be taken from their sub-transient reactances.
Figure 2
(a) For the network shown in Figure 2, construct the bus impedance matrix Z
by adding one element at a time and using the node elimination technique, where necessary. If there is a 3-phase fault through a reactance of 0.1 pu at bus 2, calculate the fault current in pu and in Ampere. Calculate the voltage magnitudes at buses 1 and 2 under the fault condition. Assume that no current was flowing prior to the fault and that the pre-fault voltage at bus
2 was at 1.0 per unit. (10 Marks)
(b) If there is a 3-phase fault through a reactance of 0.1 pu at the middle of
the line, calculate the fault current in Ampere and in per unit. (5 Marks)
Question 4.
15 Marks
Equipment ratings and per unit reactances for the power system in Figure 3 are given as follows:
Figure 3
Synchronous Generators
G1 100 MVA 25 kV X1=X2=0.2 X0=0.05
G2 100 MVA 13.8 kV X1=X2=0.2 X0=0.05
Transformers
T1 100 MVA 25/230 kV X1=X2= X0=0.05
T2 100 MVA 13.8/230 kV X1=X2= X0=0.05
Transmission Lines
TL12 |
100 MVA |
230kV |
X1=X2=0. 1 |
X0=0.3 |
TL13 |
100 MVA |
230kV |
X1=X2=0.1 |
X0=0.3 |
TL23 |
100 MVA |
230kV |
X1=X2=0 . 1 |
X0=0 .3 |
(a) Using a 100 MVA, 230 kV base for the transmission lines, draw the per unit
positive, negative and zero sequence networks and reduce them to their Thevenin equivalents, ‘looking in’ at bus 3. Neglect -Y phase shifts.
(6 Marks) (b) Compute the fault current in pu at the fault for the following faults at bus
3. (6 Marks)
(i) A bolted single line to ground fault (ii) A bolted double line to ground fault.
(c) Also, for the single line to ground fault at bus 3, determine the voltages at the terminals of generators G1 and G2. (3 Marks)
Question 5. 15 Marks
A one generator infinite bus power system is shown in Figure 4. Data for the system is given as follows: H= 7.5 MJ/MVA; Frequency=50 Hz, MVA Base= 100 MVA, G: X1=X2=j0.26 pu, X0= j0.12 pu; T1 and T2: X1=X2= X0= j0. 12 pu; Line 1 and Line 2: X1=X2=j0.42 pu, X0= j01.26 pu
(a) Initially EG=E(∞)=1.0 pu and P0=0.8 pu. When the mechanical power is increased suddenly to 1.25 pu, calculate the maximum value of 6 (6m) for which the system will remain stable. Derive any necessary equation. (7 Marks)
(b) While operating at its initial state, a three phase fault occurs at the point a, and the fault is cleared by itself at a time tc which corresponds to 6c=70o . Analyse
the stability of the system for this condition. (8 Marks)
Figure 4
2022-07-14